Chapter 2

Installation

Electrical Terminations for
Input and Output Power

Customer power cables (3-phase input, 3-phase output to protected loads) enter
the top of the Automatic Bypass Switchboard enclosure at the location labeled
CUSTOMER CONNECTION ENTRANCE in

Figure 1

. The top panel

should be removed to punch conduit holes. Bus bar locations and hole pattern are
shown in

Figure 4

.

Utility Input and Load Wiring

Connect incoming earth ground conductor to the GROUND bus bar in
accordance with the National Electrical Code and local codes.

UTILITY INPUT

cables are terminated at bus bars labeled (left to right)

L1

L2

L3

The Neutral input cables are terminated at the bus bar labeled

• NEUTRAL

(For 4-wire systems only: Neutral connection is

required for proper operation)

OUTPUT FOR PROTECTED LOADS

cables are terminated

at bus bars labeled

X1

X2

X3

The Neutral output cables, if needed, are terminated at the same bus bar
labeled

• NEUTRAL

(present only in 4-wire systems)

Put Automatic Bypass Switchboard circuit breakers in these positions
before energizing the system:

CBI = OFF (open)

CBB = ON (closed)

CBO = OFF (open)

Replace all insulating panels, covers, close and lock all doors
before energizing the system.