Rockwell Automation 1608M MegaDySC User Manual, 800 - 2400 A User Manual

Page 37

Advertising
background image

37

Rockwell Automation Publication 1608M-UM002A-EN-P - September 2013

Chapter 7

Maintenance

31

CONFIG

Configuration Alert

Call Service

Inverter

Controller configuration has changed.

Call service.

32

CNTRL_MEM

Controller Memory Busy

Auto-Resetting

Inverter

Controller is loading new data into Flash memory.

No action needed.

33

UNBALANCE

Start-Up Test: DC Bus Unbalance

Call Service

Inverter

Positive and negative halves of the DC bus did not charge equally during power up.

Call service.

34

AC_V_CHK

Start-Up Test: AC Voltage Check

Call Service

Inverter

Output voltage was detected out of tolerance during the start-up test.

Call service.

35

ROLL_CALL

Start-Up Test: Controller Roll Call Timeout

Call Service

Unit

Controller communication problem detected during start-up test.

Call service.

36

COM_VER

Start-Up Test: Communication Compatibility
Mismatch

Call Service

Unit

Firmware communication compatibility problem detected during start-up test.

Call service.

37

CNFG_TO

Start-Up Test: Controller Configuration Timeout

Call Service

Unit

Controller communication problem detected during start-up test.

Call service.

38

CNFG_ERR

Start-Up Test: Controller Configuration
Mismatch

Call Service

Unit

Controller firmware configuration problem detected during start-up test.

Call service.

39

FIRM_TO

Start-Up Test: Controller Firmware Check
Timeout

Call Service

Unit

Controller communication problem detected during start-up test.

Call service.

40

FIvRM_DIFF

Start-Up Test: Controller Firmware Revision
Mismatch

Call Service

Unit

Controller firmware revision mismatch detected during start-up test.

Call service.

41

SRL_TO

Start-Up Test: Controller Serial Number Check
Timeout

Call Service

Unit

Controller communication problem detected during start-up test.

Call service.

42

SRL_DIFF

Start-Up Test: Serial Number Mismatch

Informational

Unit

Controller serial number mismatch detected during start-up test.

No action needed.

44

T_INV_TO

Inverter Test Timeout

Call Service

Unit

Phase control board failed to respond to Comm board's Inverter test.

Call service.

46

DOOR_OPEN

DySC Cabinet Door Open

Manual Reset

Unit

DySC door was opened. Mechanical bypass commanded.

Close door. Manually reset DySC.

47

CRIT_OT

Critical Over-Temperature

Manual Reset

Unit

Internal DySC temperature exceeded maximum rating. Mechanical bypass
commanded.

Verify ambient temperature is within DySC
specification. Check for damaged fans.
Check for dirty or obstructed air filters.
Manually reset DySC.

48

FUSE_OPEN

Fuse Open

Call Service

Unit

One of the DySC fuses was detected open. Mechanical bypass commanded.

Call service.

49

OPEN_SCR_A

Open SCR Phase A

Call Service

Static Switch

The SCR on the phase A module was detected open.

Call service.

50

OPEN_SCR_B

Open SCR Phase B

Call Service

Static Switch

The SCR on the phase B module was detected open.

Call service.

51

OPEN_SCR_C

Open SCR Phase C

Call Service

Static Switch

The SCR on the phase C module was detected open.

Call service.

52

EXT_MB

External Mechanical Bypass Command

Manual Reset

Unit

The DySC was externally commanded to transfer to mechanical bypass.

Manually reset DySC.

53

DYN_BRAKE

Dynamic Brake Error

Call Service

Unit

A problem was detected with the DySC dynamic brake controller.

Call service.

54

SLAVE_OL

Critical Slave Cabinet Overload

User Attention

Unit

Slave cabinet current exceeded maximum rating. Mechanical bypass commanded.

Verify proper current sharing among slave
cabinets. Verify proper DySC application.
Call service.

55

MSTR_A_UV

Phase A Master Controller Under-Voltage

Call Service

Unit

Phase A master controller power supply failure. Mechanical bypass commanded.

Call service.

56

MSTR_B_UV

Phase B Master Controller Under-Voltage

Call Service

Unit

Phase B master controller power supply failure. Mechanical bypass commanded.

Call service.

57

MSTR_C_UV

Phase C Master Controller Under-Voltage

Call Service

Unit

Phase C master controller power supply failure. Mechanical bypass commanded.

Call service.

58

PLC_ERR

Programmable Logic Controller Error

Call Service

PLC

PLC error detected.

Call service.

Event

Code

Code Name

Full Name

Severity

Area

Event Description

Event Resolution