6 - install a hardwired stop, Chapter 6, Step 6 - install a hardwired stop – Rockwell Automation 1329I Integrated AC Drive/Motor, Series A User Manual
Page 23
 
1329I-5.0 Integrated Drive/Motor — January, 1999
Chapter
6
Step 6 - Install a Hardwired Stop
Depending upon the requirements of the application, the 1329I unit can be set up to 
provide either a coast-to-rest (default) or a ramp-to-rest (user option) operational stop. 
The unit’s Function Loss input provides an additional coast-to-rest operational stop.
In addition to the operational stop, the user must provide a hardwired stop external to 
the unit. The hardwired stop circuit must contain only hardwired electromechanical 
components. Operation of the hardwired stop must not depend on electronic logic 
(hardware or software) or on the communication of commands over an electronic 
network or link.
ATTENTION: The user must provide an external, hardwired stop circuit 
outside of the 1329I unit circuitry. This circuit must disable the system 
in case of improper operation. Uncontrolled machine operation may result 
if this procedure is not followed. Failure to observe this precaution could 
result in bodily injury.