11 - diagnostics and troubleshooting, Diagnostics and troubleshooting, Chapter – Rockwell Automation 1329I Integrated AC Drive/Motor, Series A User Manual
Page 51
 
1329I-5.0 Integrated Drive/Motor — January, 1999
Chapter
11
Diagnostics and Troubleshooting
Use the following flowchart to troubleshoot the unit.
ATTENTION: Only qualified personnel familiar with the construction 
and operation of this equipment and the hazards involved should install, 
adjust, operate, and/or service this equipment. Read and understand this 
instruction manual in its entirety before proceeding. Failure to observe 
this precaution could result in severe bodily injury or loss of life. 
ATTENTION: After disconnecting input power, wait five minutes and 
check with a voltmeter to assure that DC bus capacitors are discharged. 
The voltmeter should read zero volts. Failure to observe these precautions 
could result in severe bodily injury or loss of life.
ATTENTION: If a megohmmeter (megger) is used, make certain that all 
leads are disconnected between the motor and the drive. This will prevent 
damage to electronic circuitry due to high voltage generated by the 
megger. Use three wires to megger to ground. Failure to observe this 
precaution could result in damage to, or destruction of, the equipment.
Is display on?
Is fault displayed?
Define nature
of problem.
See Table 11.2 in
Section 11.2
Motor will not start.
Motor rotates
but does not
accelerate
to full speed.
Motor stops
while running.
Motor runs, but
not with expected
performance.
See Section 11.1
See Table 11.3 in
Section 11.2
See Table 11.4 in
Section 11.2
See Table 11.5 in
Section 11.2
See Table 11.6 in
Section 11.2
Yes
Yes
No
No