Chapter 8, Chapter – Rockwell Automation 1329I Integrated AC Drive/Motor, Series A User Manual
Page 35
 
1329I-5.0 Integrated Drive/Motor — January, 1999
Chapter
8
Step 8 - Verify the Setup and Adjust
Switches if Required
The 1329I unit is set up using two rotary switches and a 10-position DIP switch mounted 
on the printed circuit board as shown in Figure 8.1. Figure 8.1 shows the setting 
selections and the factory defaults. Normally, no adjustments will be needed to the 
factory settings.
If your application requires adjustment to these settings, refer to the following sections 
in this chapter. If no adjustment is needed, go to Chapter 9 to complete the installation 
procedure.
Review all setup instructions thoroughly before making any adjustments or applying 
power to the unit.
After changing the setup, go to Chapter 9 to complete the installation.
Before making any adjustments to the unit, be sure to take the following precautions:
1. Turn off, lockout, and tag AC input power to the unit.
2. Wait five minutes. Then remove the cover and use a voltmeter to verify that the
DC bus capacitors are discharged. The voltmeter should read zero volts. Refer to 
Figure 5.2 for the DC bus test points.
ATTENTION: Only qualified personnel familiar with the construction 
and operation of this equipment and the hazards involved should install, 
adjust, operate, and/or service this equipment. Read and understand this 
instruction manual in its entirety before proceeding. Failure to observe 
this precaution could result in severe bodily injury or loss of life. 
ATTENTION: All adjustments to these components should be made with 
power removed. Failure to observe this precaution could result in severe 
bodily injury or loss of life.
ATTENTION: After disconnecting input power wait five minutes and 
check with a voltmeter to assure that DC bus capacitors are discharged. 
The voltmeter should read zero volts. Failure to observe this precaution 
could result in severe bodily injury or loss of life.
ATTENTION: The cover screws must be securely tightened in order to 
properly ground the cover. Verify that all four cover screws are tight before 
applying power to the unit. Failure to observe this precaution could result 
in severe bodily injury or loss of life.