Use rslinx or the logix designer application, Set the network ip address with rslinx software – Rockwell Automation 1756-L72EROMS Armor GuardLogix Controller User Manual

Page 14

Advertising
background image

14 Armor GuardLogix Controller

Rockwell Automation Publication 1756-IN060B-EN-P - November 2013

9. Click Disable BOOTP/DHCP.

Use RSLinx or the Logix Designer Application

This table describes when to set the network IP address with RSLinx software or the Logix
Designer application.

Set the Network IP Address with RSLinx Software

Follow these steps to use RSLinx software to set the communication module’s IP address.

1. From the Communications menu, choose RSWho.
2. From the RSWho dialog box, navigate to the Ethernet network.
3. Right-click the EtherNet/IP module and choose Module Configuration.

IMPORTANT

If you do not click Disable BOOTP/DHCP, the host controller clears the current IP
configuration and begins sending BOOTP requests again each time power is cycled.

Conditions

Use

Page

A BOOTP server is not available.
The EtherNet/IP communication module is connected to another NetLinx network.

RSLinx software

14

The Logix Designer project is online with a controller that communicates to or through
the EtherNet/IP communication module.

Logix Designer application

16