6 Armor GuardLogix Controller

Rockwell Automation Publication 1756-IN060B-EN-P - November 2013

Install the Armor GuardLogix Controller

The controller ships with the power switch inside the enclosure set to ON and the controller in
Remote Program mode. You can make power connections and EtherNet/IP network
connections without opening the access door on the enclosure. However, if you need to access
the power switch, USB port, or SD card, you will need to open the enclosure door.

Follow these steps, described in this publication, to install the controller.

1.

Mount the Controller

2.

Ground the Controller

3.

Open the Access Door

, optional

4.

Remove and Install the SD Card

, optional

5.

Connect to the USB Port

, optional

6.

Make Network Connections

7.

Make Power Connections

8.

Set the Network IP Address of the EtherNet/IP Modules

9.

Update the Controller

Mount the Controller

Observe these minimum spacing
requirements around the enclosure.

Mounting feet can be attached in either
horizontal or vertical orientation as shown
in

Product Dimensions on page 7

. Attach

the mounting feet to the enclosure by using
the four flat-head screws supplied with the
mounting feet. Torque screws to 8.5 N•m
(75.2 lb-in).

Mount the module directly to a machine by
using four mounting holes. The mounting
hole diameter on the mounting feet
included with the enclosure is 6.8 mm (0.27
in.). Use four M6 screws and torque screws
to 6.6 N•m (58 lb-in). See the

Product Dimensions on page 7

.

ATTENTION: Make sure all connectors and caps are securely tightened to properly seal
connections against leaks and maintain IP67 requirements.

30 mm (1.18 in.)

30 mm (1.18 in.)

30

mm

(1

.18 i

n.)

30 m

m

(1

.1

8 in.)