Armor GuardLogix Controller 9

Rockwell Automation Publication 1756-IN060B-EN-P - November 2013

Follow these steps to install the SD card.

1. Open the access door on the enclosure.
2. Verify that the SD card is locked or unlocked according to your preference.

3. Insert the SD card into the SD card slot.
4. Gently press the card until it clicks into place.
5. Close the enclosure access door.

Connect to the USB Port

The controller has a USB port that uses a Type B receptacle. The port is USB 2.0-compatible and
runs at 12 M. To use the USB port of the controller, you must have RSLinx® software, version
2.59 or later, installed on your workstation.

Access the USB port by opening the enclosure door.

Use a USB cable to connect your workstation to the USB port. With this connection, you can
upgrade firmware and download programs to the controller directly from your workstation.

ATTENTION: If you are not sure of the contents of the memory card, before you install the
card, turn the keyswitch of the controller to the PROG position. Depending on the contents of
the card, a power cycle or fault could cause the card to load a different project or operating
system into the controller.

ATTENTION: The USB port is intended for only temporary local programming purposes and
not intended for permanent connection.

The USB cable must not exceed 3.0 m (9.84 ft) and must not contain hubs.

Unlocked

Locked

Logix 55xx

RUN FORCE SD OK