Foundation Fieldbus Linking Device 19

Publication

1757-IN021E-EN-P - August 2009

Reset Configuration

The Reset Configuration removes power from the battery, clearing all
downloaded fieldbus configurations. The linking device retains its network
configuration and web page password information through this reset.

Do these steps to reset configuration.

1. Remove power from the linking device.

2. Move the jumper from its original position (two right pins) to the two

left pins.

3. Wait 5 seconds.

4. Move the jumper back to its original position.

5. Return power to the linking device.

Reset to Factory Default

The factory-default reset sets the linking device’s network configuration to use
BOOTP, erases web page password information, and clears all downloaded
fieldbus configurations. Follow these steps to complete a factory-default reset.

1. Verify that the linking device is powered up and in a running state

(H1 status indicators are blinking).

2. Press the reset button.

WARNING

If you insert or remove the jumper while the power is on, an electrical arc can
occur. This could cause an explosion in hazardous location installations. Be
sure the area is nonhazardous before proceeding.

WARNING

When you press the reset button while power is on, an electrical arc can occur.
This could cause an explosion in hazardous location installations. Be sure that
power is removed or the area is nonhazardous before proceeding.