Install the linking device – Rockwell Automation 1757-FFLD4 Foundation Fieldbus Linking Device Installation Instructions User Manual

Page 7

Advertising
background image

Foundation Fieldbus Linking Device 7

Publication

1757-IN021E-EN-P - August 2009

Before You Begin

The following software is compatible with this revision of the linking device:

• RSFieldbus software, version 2.03 or later

• RSLogix 5000 programming software, version 16.03 or later

• RSLinx Classic software, version 2.52 or later

• Logix5000 Clock Update tool

Install the Linking Device

Install your linking device by using the instructions on the following pages.

Mount the Linking Device

Most applications require installation in an industrial enclosure (Pollution
Degree 2) to reduce the effects of electrical interference (Over Voltage
Category II) and environmental exposure. Locate your linking device as far as
possible from power lines, load lines, and other sources of electrical noise
such as hard-contact switches, relays, and AC motor drives. For more
information on proper grounding guidelines, see the Industrial Automation
Wiring and Grounding Guidelines, publication

1770-4.1

.

ATTENTION

We do not recommend vertical mounting due to heat build-up
considerations.

Be careful of metal chips when drilling mounting holes for your linking
device or other equipment within the enclosure or panel. Drilled
fragments that fall into the unit could cause damage.

Advertising
This manual is related to the following products: