Rockwell Automation 1757-FFLD4 Foundation Fieldbus Linking Device Installation Instructions User Manual

Page 20

Advertising
background image

20 Foundation Fieldbus Linking Device

Publication

1757-IN021E-EN-P - August 2009

Status Indicators

Linking Device Status Indicators

Indicator

Status

Description

H1

Off

The linking device H1 channel is inactive.
Verify that the linking device is connected to the H1 network.

Flashing green The linking device H1 channel is active.

STATUS
(module)

Off

No power - Module does not have 24V DC power.
Verify that power is supplied to the module.

Flashing green Standby - Module not configured.

(1)

Green

Operational - Module operating correctly.

Flashing red

Minor fault - A recoverable fault has been detected.
Verify that the configuration is correct and consistent.

Red

Major fault - An unrecoverable fault has been detected.
Recycle power to the module. If this does not clear the fault,
replace the module.

WDOG
(watchdog)

Off

Normal operation.

Flashing red

Software fault.
Contact Rockwell Automation Technical Support.

BATT
(battery)

Off

Normal operation.

Flashing red

Jumper is missing (or not seated on the two rightmost pins), or

the battery is low or dead.

(2)

NS
(network
status)

Off

Not powered, no IP address.
Verify that power is supplied or assign an IP address.

Flashing green No connections.

(1)

Verify that the linking device is connected to the fieldbus
network.

Green

CIP connections.

Flashing red

Connection timeout.
Verify that the linking device is connected to the Ethernet
network.

Flashing red
and green

Self test.