Rockwell Automation 1757-FFLD4 Foundation Fieldbus Linking Device Installation Instructions User Manual

Page 22

Advertising
background image

22 Foundation Fieldbus Linking Device

Publication

1757-IN021E-EN-P - August 2009

Wiring category

(2)

2 - on Fieldbus ports

3 - on power ports

2 - on Ethernet ports

Terminal block torque specifications

0.34 N•m (3 lb•in) on power and Fieldbus
wire connections

Wire size

DC power connection

Fieldbus connections

Ethernet connections

0.2... 1.5 mm

2

(26...16 AWG) solid or

stranded copper wire rated at 75 °C (167 °F)
or greater 1.2 mm (3/64 in.) insulation max

0.8 mm

2

(18 AWG) solid or stranded

shielded twisted pair copper wire rated at
75 °C (167 °F) or greater 1.2 mm (3/64 in.)
insulation max

RJ45 connector according to IEC 60603-7,
2 or 4 pair Category 5e minimum cable
according to TIA 568-B.1 or Category 5
cable according to ISO/IEC 24702

Program retention (unpowered)

21 days

North American temp code

T4

IEC temp code

T4

In-circuit battery life

5000 charge/discharge cycles (about 13
years). Battery is not replaceable

Enclosure type rating

None (open-style)

(1)

Each network defined as a FOUNDATION Fieldbus 31.25 kbps H1 network.

(2)

Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication

1770-4.1

.

1757-FFLD2, 1757-FFLD4 - Technical Specifications