Rockwell Automation 1768-L43_L45_L43S_L45S CompactLogix Controllers Installation Instructions User Manual

Page 19

Advertising
background image

CompactLogix Controllers 19

Publication

1768-IN004D-EN-P - December 2009

Updating your controller firmware via ControlFlash or AutoFlash
software requires either a serial or other network connection to the
controller.

Updating via an Ethernet connection is faster, but you must first
install a 1768-ENBT Ethernet module to connect to the controller via
the Ethernet network.

For information on installing, configuring, and operating a
1768-ENBT module, refer to the EtherNet/IP Modules in Logix5000
Control Systems User Manual, publication

ENET-UM001

.

Install Firmware via ControlFlash Software

1. Make sure the network is connected.

2. Start ControlFlash software.

3. When the Welcome dialog box appears, click Next.

4. Select the catalog number of the controller and click Next.

5. Expand the network until you see the controller.

6. Select the controller and click OK.

7. Select the desired revision level and click Next.

8. To start the update, click Finish and then Yes.

The OK status indicator flashes red to show that the update is
in progress. The status box indicates when the update is
complete and the OK status indicator is solid green.

9. Click OK.

10. Click Cancel and then Yes to close ControlFlash software.

TIP

If the required network is not shown, first configure a driver for that
network in RSLinx software.

Advertising