CompactLogix Controllers 25

Publication

1768-IN004D-EN-P - December 2009

Safety Status Indicators (1768-L43S and 1768-L45S Controllers only)

Indicator

State

Description

SAFE RUN

Off

The user safety task or safety outputs are disabled.
The controller is in PROG mode, Test mode, or the
safety task is faulted.

Green

The user safety task and safety outputs are enabled.
The safety task is executing. Safety signature is
present.

Flashing green

The user safety task and safety outputs are enabled.
The safety task is executing. Safety signature is not
present.

SAFETY
TASK

Off

No partnership established.

Green

Safety controller status is OK. The coordinated
system time (CST) is synchronized and safety I/O
connections are established.

Flashing green

Safety controller status is OK. The coordinated
system time (CST) is not synchronized.

Red

Safety partnership was lost.

Flashing red

Safety task is inoperable.

SAFETY
LOCK

Off

Safety task is not locked.

Green

Safety task is locked.

SAFETY OK

Off

No power is applied.

Green

The safety partner is OK.

Flashing green

The safety partner is storing or loading a project to
or from nonvolatile memory.

Red

The safety partner detected a nonrecoverable major
fault, so it cleared the project from its memory.

Flashing red

The internal safety partner requires a firmware
update or a firmware update is in progress.

A recoverable major fault occurred on the
safety partner.

A nonrecoverable major fault occurred on the
safety partner.