Controller Status Indicators

Indicator

State

Description

PWR

Green

The controller is providing power to 1768 modules in
the system.

Off or red

See

Troubleshoot System Power on page 28

.

I/O PWR

Off

Replace the controller.

Green

The controller is operating properly.

Flashing red/green
or solid red

See

Troubleshoot System Power on page 28

.

RUN

Off

The controller is in PROG or Test mode.

Green

The controller is in RUN mode.

FORCE

Off

No tags contain I/O force values or I/O forces are
inactive (disabled).

Amber

I/O forces are active (enabled). I/O force values may or
may not exist.

Flashing amber

One or more input or output addresses have been
forced to an On or Off state, but the forces have not
been enabled. Enable forces or remove the individual
I/O from being forced.

MEM
SAVE

Off

The user program and configuration data are not
actively being saved to flash memory.

Green

The use program and configuration data are being
saved to flash memory.

I/O

Off

There are no devices in the I/O configuration of the
controller or the controller does not contain a project.

Green

The controller is communicating with all of the devices
in its I/O configuration.

Flashing green

One or more devices in the controller’s I/O configuration
are not responding.
See

Troubleshoot a Nonresponsive Module on page 27

.

Flashing red

The controller is not communicating with any of the
devices in its I/O configuration.
See

Troubleshoot a Nonresponsive Module on page 27

.