4 CompactLogix Controllers

Publication

1768-IN004D-EN-P - December 2009

European Hazardous Location Approval

Consider the following if you install a 1768-L43S or 1768-L45S
controller in a European Zone 2 location.

General Safety Information for 1768-L43S and 1768-L45S Controllers

European Zone 2 Certification (The following applies when the product bears the
EX marking.)

This equipment is intended for use in potentially explosive atmospheres as defined by
European Union Directive 94/9/EC and has been found to comply with the Essential Health
and Safety Requirements relating to the design and construction of Category 3 equipment
intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this
Directive.

Compliance with the Essential Health and Safety Requirements has been assured by
compliance with EN 60079-15 and EN 60079-0.

WARNING

This equipment must be installed in an enclosure providing at least IP54
protection when applied in Zone 2 environments.

This equipment shall be used within its specified ratings defined by
Allen-Bradley.

Provision shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 40% when applied in
Zone 2 environments.

This equipment is not resistant to sunlight or other sources of UV
radiation.

Secure any external connections that mate to this equipment by using
screws, sliding latches, threaded connectors, or other means provided
with this product.

Do not disconnect equipment unless power has been removed or the
area is known to be nonhazardous.

ATTENTION

Personnel responsible for the application of safety-related programmable
electronic systems (PES) shall be aware of the safety requirements in the
application of the system and shall be trained in using the system.