CompactLogix Controllers 29

Publication

1768-IN004D-EN-P - December 2009

Examine the Power Supply PWR Status Indicator

1. Remove power and wait for all status indicators to turn off.

2. Disconnect all modules from the system, including the

controller.

3. Reapply power.

4. Check the PWR status indicator on the power supply.

a. If the status indicator remains red, replace the power

supply.

b. If the status indicator is green, one of the other modules in

the system is causing the red indicator.

5. Remove power and wait for all status indicators to turn off.

6. Reinstall the controller and check the power supply’s PWR

indicator.

a. If green, remove power, wait for all status indicators to turn

off and reinstall 1768 modules one at a time until you
identify the module causing the red indicator.

b. If red, replace the controller.

Power Supply PWR
Indicator Status

Recommended Action

Off

Verify that the power supply is turned on and that adequate input
power is properly connected.
Replace the power supply.

Green

The power supply is operating properly.
Check the controller PWR and I/O PWR status indicators to make
sure the entire system is operating properly.

Red

The power supply is not producing valid 24V power to the 1768
modules. Follow the corrective action below.