24 CompactLogix Controllers

Publication

1768-IN004D-EN-P - December 2009

OK

Off

No power is applied. If MEM SAVE indicator is green,
the user program and configuration data are being
saved to flash memory.

Flashing red

The controller requires a firmware update or a
firmware update is in progress.

A recoverable major fault occurred on the
controller.

A nonrecoverable major fault occurred on the
controller.

See

Clear a Major Fault on page 26

.

Red

The controller detected a nonrecoverable major fault so
it cleared the project from memory.
See

Clear a Nonrecoverable Fault on page 27

.

Green

Controller is OK.

Flashing green

The controller is storing or loading a project to or from
nonvolatile memory.

CF

Off

There is no CompactFlash card activity.

Flashing green

The controller is reading from or writing to the
CompactFlash card.

IMPORTANT: Do not remove the CompactFlash card
while the controller is reading from or writing to the
card. Removing the card during a read or write could
corrupt data on the card, data in the controller, and
firmware installed on the controller.

Flashing red

The CompactFlash card does not have a valid file
system and must be replaced.

DCH0

Off

Channel 0 is configured differently than the default
serial configuration.

Green

Channel 0 has the default serial configuration.

CH0

Off

No RS-232 activity.

Green

RS-232 activity.

Controller Status Indicators

Indicator

State

Description