Ethernet PLC-5 Programmable Controllers 11

4. To send email, enter the appropriate information into the Data fields

and Username and Password, if Authentication is enabled.

Examine the Error Code (denoted in Hex) and Error Description areas within
the General tab to see if the message was successfully delivered.

Channel 2 Status

To check the status of channel 2:

1. In your RSLogix 5 software project, click on Channel Status.

You see the Channel Status menu.

2. Click on the Channel 2 tab.

3. Click on the Port tab.

You see the status for each port configuration.

Error Code (hex)

Description

0x000

Delivery successful to the mail relay server.

0x002

Resource unavailable. The email object was unable to obtain memory resources to initiate the SMTP session.

0x101

SMTP mail server IP address not configured.

0x102

To (destination) address not configured or invalid.

0x103

From (reply) address not configured or invalid.

0x104

Unable to connect to SMTP mail server.

0x105

Communication error with SMTP server.

0x106

Authentication required.

0x017

Authentication failed.