Publication 1785-IN063B-EN-P - January 2006

Ethernet PLC-5 Programmable Controllers 17

Install the PLC-5 Programmable Controller

The controller is a modular component of the 1771 I/O system requiring a
properly installed system chassis. Refer to publication 1771-IN075 for detailed
information on acceptable chassis along with proper installation and
grounding requirements. Limit the maximum adjacent slot power dissipation
to 10 W.

1. Define the DH+ Station Address of Channel 1A by setting switch

assembly SW-1 on the back of the controller.

See the side of the controller for a listing of DH+ switch settings.

2. Specify the Channel 0 port configuration. See the side of the controller

for a listing of Channel 0 switch settings.

43913

Side View of Controller Switch Assembly SW1

Use Switch 7 to Set the Communication Rate

Side View of Switch 7

Up
230 Kbps

Down
57.6 Kbps

1 2 3 4 5 6 7

10

Front of
Controller

Bottom View of Controller
Switch Assembly SW2

Side View

OFF

1 2 3 4 5 6 7 8 9