Install the PLC-5 Programmable Controller
The controller is a modular component of the 1771 I/O system requiring a
properly installed system chassis. Refer to publication 1771-IN075 for detailed
information on acceptable chassis along with proper installation and
grounding requirements. Limit the maximum adjacent slot power dissipation
to 10 W.
1. Define the DH+ Station Address of Channel 1A by setting switch
assembly SW-1 on the back of the controller.
See the side of the controller for a listing of DH+ switch settings.
2. Specify the Channel 0 port configuration. See the side of the controller
for a listing of Channel 0 switch settings.
43913
Side View of Controller Switch Assembly SW1
Use Switch 7 to Set the Communication Rate
Side View of Switch 7
Up
230 Kbps
Down
57.6 Kbps
1 2 3 4 5 6 7
10
Front of
Controller
Bottom View of Controller
Switch Assembly SW2
Side View
OFF
1 2 3 4 5 6 7 8 9
43914