Controller specifications – Rockwell Automation 1785-Lx0E Ethernet PLC-5 Programmable Controllers Installation Instructions User Manual

Page 24

Advertising
background image

Publication 1785-IN063B-EN-P - January 2006

24 Ethernet PLC-5 Programmable Controllers

Controller Specifications

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0...60

o

C (32...140

o

F)

Nonoperating Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Nonoperating Cold),
IEC 60068-2-2 (Test Bc, Un-packaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Nonoperating Thermal Shock):
–40...85

o

C (–40...185

o

F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Nonoperating

Damp Heat):
5...95% Noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10...500Hz

Operating Shock

IEC 60068-2-27:1987, (Test Ea, Unpackaged shock):
30 g

Nonoperating Shock

IEC 60068-2-27:1987, (Test Ea, Unpackaged shock):
50 g

Emissions

CISPR 11:
Group 1, Class A (with appropriate enclosure)

ESD Immunity

IEC 61000-4-2:
6 kV indirect contact discharges

Radiated RF Immunity

IEC 61000-4-3:
10 V/m with 1 kHz sine-wave 80% AM from 30...2000 MHz

10 V/m with 200 Hz Pulse 50% AM from 100% AM at 900 MHz

10 V/m with 200 Hz Pulse 50% AM from 100% AM at 1890 MHz

1V/m with 1 kHz sine-wave 80%AM from 2000…2700 MHz

EFT/B Immunity

IEC 61000-4-4:
+2 kV at 5 kHz on communications ports

Surge Transient Immunity

IEC 61000-4-5:
+2 kV line-earth (CM) on communications ports

Conducted RF Immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz

Enclosure Type Rating

None (open style)

Power Consumption

3.6 A @5V dc max

Power Dissipation

18.9 W max

Isolation

(continuous voltage rating)

50V Basic Insulation between communication ports and between communication ports
and backplane

Tested to withstand 500V rms for 60 s

Wire Size

Ethernet: 802.3 compliant shielded or unshielded twisted pair
Remote I/O: 1770-CD cable
Serial Ports: Belden 8342 or equivalent

Wiring Category

(1)

2 - on communications ports

Replacement Battery

1770-XYC

North American Temp Code

T4A

Specifications continued on next page

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding
Guidelines, publication 1770-4.1.