GuardPLC 1753-IF8XOF4 Analog I/O Module 11

Publication 1753-IN013A-EN-P - September 2005

Analog Input Terminals

Analog inputs (AI) are connected to the following terminals:

Connect the Wires

See the wire size and terminal block torque specifications on page 16. The cables
are connected to the front plate of the module using pluggable terminals. Shielded
cabling is fed in from below so that the shielding can be connected to the shield
contact plate using a clip. Remove about 2 cm (3/4 in) of the outer cable insulation
so that the mesh is exposed at the point where the cable is clipped to the plate.

Terminal Number

Designation

Function

1

T1

Sensor supply 1

2

I1

Analog input 1

3

L-

Reference pole input 1

4

T2

Sensor supply 2

5

I2

Analog input 2

6

L-

Reference pole input 2

7

T3

Sensor supply 3

8

I3

Analog input 3

9

L-

Reference pole input 3

10

T4

Sensor supply 4

11

I4

Analog input 4

12

L-

Reference pole input 4

13

T5

Sensor supply 5

14

I5

Analog input 5

15

L-

Reference pole input 5

16

T6

Sensor supply 6

17

I6

Analog input 6

18

L-

Reference pole input 6

19

T7

Sensor supply 7

20

I7

Analog input 7

21

L-

Reference pole input 7

22

T8

Sensor supply 8

23

I8

Analog input 8

24

L-

Reference pole input 8