Specifications – Rockwell Automation 1753-IF8XOF4 GuardPLC 1753-IF8XOF4 Analog I/O Module User Manual

Page 16

Advertising
background image

16 GuardPLC 1753-IF8XOF4 Analog I/O Module

Publication 1753-IN013A-EN-P - September 2005

Specifications

OSL

Flashing

Emergency Operating System Loader is active.

BL

Flashing

Boot Loader unable to load operating system or unable to start COMM operating
system loader.

Controller status can be interrogated through the programming software. For more information, refer to the
GuardPLC™ Controller Systems User Manual (1753-UM001).

General

Interfaces: GuardPLC Ethernet

2 x RJ-45, 10/100BaseT (with 100 Mbps) with integrated switch

Operating Voltage

24V dc, -15% to +20%, w

ss

15% from a power supply with protective

separation, conforming to IEC 61131-2 requirements, as well as either
of the following:

• EN 60950 - SELV (Safety Extra Low Voltage)

• EN 60204 - PELV (Protective Extra Low Voltage)

Response Time

≥ 20 ms

Battery Backup

none

Current Consumption

max. 0.8 A (with max. load), idle current 0.4 A @24V

Isolation Voltage

No isolation between circuits

Wiring Category

(1)

category 2 on communications ports, signal ports, and power ports

Wire Size

I/O – 16 AWG (1.5 mm

2

) to 26 AWG (0.14 mm

2

) solid or stranded copper

wire rated at 75 °C (167 °F) or greater with 3/64 inch (1.2 mm) insulation
maximum

Power – 14 AWG (2.5 mm

2

) to 22 AWG (0.34 mm

2

) solid or stranded

copper wire rated at 75 °C (167 °F) or greater with 3/64 inch (1.2 mm)
insulation maximum

Terminal Block Torque

0.51 Nm (4.5 in-lb)

Indicator

State

Condition