12 GuardPLC 1753-IF8XOF4 Analog I/O Module

Publication 1753-IN013A-EN-P - September 2005

Position the clip over the uninsulated cable shielding and push it into the slots of

the shield contact plate until it fits firmly in place, as shown below.

Standard Analog Outputs

The module has 4 analog outputs, which are not safety-rated outputs. However, in
the event of an internal error, they can be shut down safely through configuration
via the user program.

The following output values are available:

IMPORTANT

Make sure that the mesh comes in direct contact with the shield
contact plate. If the mesh does not touch the plate, the cable is
not grounded.

ATTENTION

To achieve SIL 3, the output values must be read back via safety
analog inputs and evaluated in the RSLogix Guard PLUS! user
program. Otherwise, they may not be used as safety outputs.

Value Range in the Application

Output Current

0

0 mA

2000

20 mA