Analog cabling should be no more than 300 m (984 ft) in length and must be
shielded, twisted-pair cables for each measurement input. The shields must be
connected at one end.

Analog Input Values

The following input values are available:

Voltage Measurment

If an open-circuit fault occurs during voltage measurement, unpredictable input
signals are received on the high resistance inputs. Values resulting from this
fluctuating input voltage are not reliable. Because the module does not feature
circuit monitoring, you must terminate input channels with a 10 k

Ω resistor when

measuring voltage. Consider the internal resistance of the source as well.

Current Measurement

To measure current, connect a 500

Ω external shunt in parallel to the input.

Accuracy of the shunt must be included in accuracy calculations of the input signal.
Terminating resistors are not required for current measurement with the external
shunt connected in parallel.

IMPORTANT

Short-circuit unused input channels to the reference pole by
connecting wire jumpers.

Input Channels

Polarity

Current or Voltage

Range

Safety Accuracy

8

unipolar

0…+10V

0…2000

2%

0…20 mA / 4…20 mA

0…1000

(1)

0…2000

(2)

(1)

with external 250

Ω shunt

(2)

with external 500

Ω shunt