18 GuardPLC 1753-IF8XOF4 Analog I/O Module

Publication 1753-IN013A-EN-P - September 2005

Environmental Conditions

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):
-40°C to +85°C (-40°F to +185°F) without backup battery

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0°C to +60°C (+32°F to +140°F)

Vibration

IEC60068-2-6 (Test Fc, Operating): 1 g @ 10…150 Hz

Shock, Operating

IEC60068-2-27 (Test Ea, Unpackaged Shock):15 g

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):
10 to 95% non-condensing

Emissions

Group 1, Class A

ESD Immunity

IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80% AM from 80 Hz to 2000 MHz

EFT/B Immunity

IEC 61000-4-4:
±2 kV @ 5 kHz on power ports
±1 kV @ 5 kHz on signal ports
±1 kV @ 5 kHz on communication ports

Surge Transient Immunity

IEC 61000-4-5:
±500V line-line (DM) and ±500 line-earth (CM) on DC power ports
±1 kV line-earth (CM) on shielded ports
±1 kV line-earth (CM) on communication ports

Conducted RF Immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz to 80 MHz

Enclosure Type Rating

meets IP20

Mechanical Dimensions

Width

207 mm (8.16 in.) including housing screws

Height

114 mm (4.49 in.) including latch

Depth

97 mm (3.82 in.) including grounding bolt

Weight

0.95 kg (2.09 lb)