Communicate with Your ArmorBlock Module

This ArmorBlock module acts as a slave in a master/slave environment.
It is both a “polled device” and a “change of state device.”

When configured as a polled device, a master initiates communication
by sending its polled I/O message to the ArmorBlock module. The 4
input module scans the inputs and fault bit producing a response that
reflects their status.

When configured as a “change of state” device, productions occur
when an input changes or an input source voltage fault occurs. If
neither has occurred within the “expected packet rate,” a heartbeat
production occurs. This heartbeat production tells the scanner module
that the ArmorBlock module is alive and ready to communicate.

Bit

07

06

05

04

03

02

01

00

Produces

S

Reserved

I3

I2

I1

I0

Where: I = Input

S = Sensor source voltage fault

Word

Bit

Description

Produces

00–03

Input bits – bit 00 corresponds to input 0, bit 01 to input 1, and
so on.
0 = input off; 1 = the input is on.

04–06

Reserved

07

Sensor source voltage fault bit – this bit is set (1) when the sensor
source voltage is faulted.