ArmorBlock 4 Input Module

Publication 1792-5.1 – October 1996

”This connection contains data from inputs at bits 0–3 and the sensor source voltage
status at bit 7.”;
[ParamClass]
MaxInst = 9;

$ 4 configurable and 5 read–only parameters

Descriptor = 0x09;

$ Stub param instances in eeprom.

CfgAssembly = 0x66;

$ The config assembly is instance #102 of assy obj.

[Params]
$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$
$$$$$$$$$$
Param1 =

$ Disable Autobaud

0,

$ reserved

6,

$ Link Path Size

”20 03 24 01 30 64”,

$ Link Path to disable autobaud attribute.

0x0002,

$ No support for settable path, scaling, scaling links,
$ or real time update of value. Value is gettable and
$ Settable. Enumerated strings are supported.

4,

$ Data Type – boolean

1,

$ Data Size

”Autobaud”,

$ Parameter Name

””,

$ Units String

$$$$$$$$$$ Help string $$$$$$$$$$$

”Enable takes effect after next powerup. Disable is required to set fixed baud rate, no
power cycle is required.”,
0,1,0,

$ Min, Max, and Default values

1,1,1,0,0,0,0,0,0;

$ Not Used

$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$
$$$$$$$$$$
Param2 =

$ Input filter Off_to_On Delay selection

0,

$ reserved

6,

$ Link Path Size

”20 0F 24 02 30 01”,

$ Link Path to param instance. The param instance
$ decodes the enumerated parameter into engineering
$ units (micro seconds).

0x0002,

$ No support for settable path, scaling, scaling links,
$ or real time update of value. Value is gettable and
$ Settable. Enumerated strings are supported.

2,

$ Data Type – unsigned int

2,

$ Data Size – (in bytes)

”Off–to–On Delay”,

$ Parameter Name

”ms”,

$ Units String

$$$$$$$$$$ Help string $$$$$$$$$$$

”Signal must be present for this delay period before module detects the change.”,
0,4,0,

$ Min, Max (max enumeration #), and Default values

1,1,1,0,0,0,0,0,0;

$ Not Used

$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$
$$$$$$$$$$
Param3 =

$ Input filter On_to_Off Delay selection

0,

$ reserved

6,

$ Link Path Size