10 GuardPLC 8-Digital Inputs and 8-Digital Outputs Module

Publication 1753-IN010A-EN-P - October 2005

Devices with their own dedicated power supply can also be connected. Connect
the reference pole of the external power supply to the L- reference pole of the
input.

The safety state of an input is indicated by a 0 signal being passed to the user
program logic. If the test routines detect a fault in the digital inputs, a 0-signal is
processed in the user program for the defective channel. When a fault occurs, the
inputs are switched off (0) and the fault LED indicator is activated.

Follow the closed-circuit principle for external wiring when connecting sensors. To
create a safety state in the event of a fault, the input signals revert to the
de-energized state (0). Although the external line is not monitored, a wire break is
interpreted as a safe 0-signal.

TIP

For more information on input wiring, see the GuardPLC
System User Manual, publication number 1753-UM001.

PO PULSE TEST

L-

L-

L+ L+

1

LS+

LS+

L-

2 3 4

5

L-

DI

D1

6 7 8

19 20 21 22 23 24

1

L-

L-

2 3 4+

7 8 9 10 11 12

25 26 27 28 29 30

24V DC

RUN

24 V DC

PROG

ERROR

FAULT

FORCE

BL

OSL

GuardPLC Ethernet

10/100 BaseT

1

( )

2

( )

1753-IB8XOB8

8 DC Inputs

8 DC Outputs

5

L-

L-

6 7 8+

13 14 15 16 17 18

1

L-

S+

2 4- 8-

1 2 3 4 5 6

DO-

DO

(2A)

(2A)

DO

L-

L-

L+

L+

24V DC

19

20 21 22 23 24

1

LS+-

L-

DI

2 3 4

24V dc
Power
Supply

COM

+

24V dc
Power
Supply

COM

COM

+

+

Light Curtain

(or any Safety Input Device)