Wire the Module
The following sections describe how to wire the module.
Ground the Module
You must also provide an acceptable grounding path for each device in your 
application. For more information on proper grounding guidelines, refer to the 
Industrial Automation Wiring and Grounding Guidelines, publication number 
1770-4.1.
The I/O module is functionally grounded through its DIN rail connection. A 
protective earth ground connection is required and is provided through a separate 
grounding screw, located on the upper left of the housing and marked with the 
grounding symbol
.
Connections for Safety-Related Communications
Ethernet Switch
The module has two 10/100BaseT, RJ-45 connectors to provide communications to 
the GuardPLC controller via GuardPLC Ethernet. The connectors are located on the 
bottom side on the left. The connectors and the module are connected together by 
an internal Ethernet switch. The switches are auto-detect. Either cross-over or 
straight-through shielded Ethernet cabling can be used.
Star or line configurations are available. Make sure that a network loop is not 
generated. Data packets must only be able to reach a node via a single path.
MAC Address
The Media Access Control (MAC) Address of the module can be found on the label 
positioned over both lower RJ-45 connections.
ATTENTION
This product is grounded through the DIN rail to chassis ground. 
Use zinc plated yellow-chromate steel DIN rail to assure proper 
grounding. The use of other DIN rail materials (e.g. aluminum, 
plastic, etc.) that can corrode, oxidize, or are poor conductors, 
can result in improper or intermittent grounding.