Rockwell Automation 1753-IB8XOB8 GuardPLC 8-Digital Inputs and 8-Digital Outputs Module Installation Instructions User Manual

Page 19

Advertising
background image

GuardPLC 8-Digital Inputs and 8-Digital Outputs Module 19

Publication 1753-IN010A-EN-P - October 2005

No. of Outputs (L-)

2 (not electrically isolated), reference pole S+

Output Voltage

≥L+ minus 2V

Output Current (L+)

Output Current (L-)

Channels 1 to 3 and 5 to 7: 0.5 A @ 60°C (140°F)
Channels 4 and 8: 1 A @ 60 °C (140 °F); 2 A @ 40 °C (104 °C)
Channels 4- and 8-: 1 A @ 60 °C (140 °F); 2 A @ 40 °C (104 °C)

Max. lamp load:
L+ channel 1-3, 5-7
L+ channel 4 and 8
L- channel 4- and 8-

10 W
25 W
25 W

Max. inductive load:
L+ channel 1-3, 5-7
L+ channel 4 and 8
L- channel 4- and 8-

500 mH
500 mH
500 mH

Minimum Load

2 mA per channel

Internal Voltage Drop

max. 2.0V dc @ 2 A

Off-State Leakage Current

max. 1 mA @

2V

Overload Response

Shut down of the concerned output with cyclic reconnection

Total Output Current

max. 7 A with exceeding shut down of all outputs with cyclic reconnection

Pulsed Outputs

No. of Outputs

2 (not electrically isolated)

Output Voltage

≥L+ minus 4V

Output Current (L+)

Approx. 60 mA

Minimum Load

none

Switching Time

≤ 100 micro-seconds

Overload Response

2 x

≥ 19.2V, short-circuit current 60 mA @ 24V

Environmental Conditions

Storage Temperature :

-40...+85 °C (-40...+185 °F)

• IEC 60068-2-1 (Test Ab, Unpackaged non-operating cold)
• IEC 60068-2-2 (Test Bb, Unpackaged non-operating dry heat)
• IEC 60068-2-14 (Test Na, Unpackaged non-operating thermal shock)

Operating Temperature:

0...+60 °C (+32...140 °F)

• IEC 60068-2-1 (Test Ad, operating cold)
• IEC 60068-2-2 (Test Bd, operating dry heat)
• IEC 60068-2-14 (Test Nb, operating thermal shock)

Vibration

1 g @ 10…150 Hz

• IEC 60068-2-6 (Test Fc, operating)

Shock, Operating

15 g

• IEC 60068-2-27 (Test Ea, unpackaged shock)

Relative Humidity

10 to 95% non-condensing

• IEC 60068-2-30 (Test Db, unpackaged non-operating damp heat)

Emissions

Group 1, Class A

ESD Immunity

6 kV contact discharges
8 kV air discharges

Advertising