Surge on digital inputs – Rockwell Automation 1753-IB8XOB8 GuardPLC 8-Digital Inputs and 8-Digital Outputs Module Installation Instructions User Manual
Page 11

GuardPLC 8-Digital Inputs and 8-Digital Outputs Module 11
Publication 1753-IN010A-EN-P - October 2005
Digital Input Terminals
See page 18 for the appropriate wire size. Digital inputs are connected to the
following terminals:
LS+, not L+, should be used for short-circuit protection. Each LS+ features individual
short-circuit and EMC protection that make it important to use LS+ for only it’s four
related inputs.
Surge on Digital Inputs
An EN 61000-4.5 surge impulse can be read as a short-time HI signal. To avoid an
error:
• install shielded input lines to prevent effects of surges in the system, or
• implement software filtering in the user program. A signal must be present
for at least two cycles before it is used by the rest of the logic in the user
program.
Terminal Number
Designation
Function
19
LS+
Sensor supply for inputs 1 to 4
20
1
Digital input 1
21
2
Digital input 2
22
3
Digital input 3
23
4
Digital input 4
24
L-
Reference pole
25
LS+
Sensor supply for inputs 5 to 8
26
5
Digital input 5
27
6
Digital input 6
28
7
Digital input 7
29
8
Digital input 8
30
L-
Reference pole
1
LS+
L-
DI
2 3 4
19 20 21 22 23 24
19 20 21 22 23 24
LS+ 5
L-
DI
6 7 8
25 26 27 28 29 30
25 26 27 28 29 30