GuardPLC 8-Digital Inputs and 8-Digital Outputs Module 11

Publication 1753-IN010A-EN-P - October 2005

Digital Input Terminals

See page 18 for the appropriate wire size. Digital inputs are connected to the
following terminals:

LS+, not L+, should be used for short-circuit protection. Each LS+ features individual
short-circuit and EMC protection that make it important to use LS+ for only it’s four
related inputs.

Surge on Digital Inputs

An EN 61000-4.5 surge impulse can be read as a short-time HI signal. To avoid an
error:

• install shielded input lines to prevent effects of surges in the system, or
• implement software filtering in the user program. A signal must be present

for at least two cycles before it is used by the rest of the logic in the user
program.

Terminal Number

Designation

Function

19

LS+

Sensor supply for inputs 1 to 4

20

1

Digital input 1

21

2

Digital input 2

22

3

Digital input 3

23

4

Digital input 4

24

L-

Reference pole

25

LS+

Sensor supply for inputs 5 to 8

26

5

Digital input 5

27

6

Digital input 6

28

7

Digital input 7

29

8

Digital input 8

30

L-

Reference pole

1

LS+

L-

DI

2 3 4

19 20 21 22 23 24

19 20 21 22 23 24

LS+ 5

L-

DI

6 7 8

25 26 27 28 29 30

25 26 27 28 29 30