12 GuardPLC 8-Digital Inputs and 8-Digital Outputs Module

Publication 1753-IN010A-EN-P - October 2005

Line Control

Line control is a short-circuit and line break monitoring system (e.g., E-Stop inputs)
which can be configured for the GuardPLC system. The example below shows 2
pulse test sources connected to the digital inputs (DI) of the same system. As a
result, the connections to the digital inputs (DI) are monitored.

Pulse Test Sources

There are two digital pulse test sources (PO) used for line control monitoring of
digital inputs. Pulse test sources are connected to the following terminals.

Terminal Number

Designation

Function

1

L-

Reference pole

2

1

Pulsed output 1

3

2

Pulsed output 2

ATTENTION

Pulsed test sources must not be used as safety-related outputs.

Emergency OFF 1

Emergency OFF 2

PO 1 2

DI 1 2

DI 3 4

1

L-

S+

PO

2 4- 8-

(2A)

1

2

3

4

5

6

1

2

3

4

5

6

DO-