Line control, Pulse test sources – Rockwell Automation 1753-IB8XOB8 GuardPLC 8-Digital Inputs and 8-Digital Outputs Module Installation Instructions User Manual
Page 12

12 GuardPLC 8-Digital Inputs and 8-Digital Outputs Module
Publication 1753-IN010A-EN-P - October 2005
Line Control
Line control is a short-circuit and line break monitoring system (e.g., E-Stop inputs)
which can be configured for the GuardPLC system. The example below shows 2
pulse test sources connected to the digital inputs (DI) of the same system. As a
result, the connections to the digital inputs (DI) are monitored.
Pulse Test Sources
There are two digital pulse test sources (PO) used for line control monitoring of
digital inputs. Pulse test sources are connected to the following terminals.
Terminal Number
Designation
Function
1
L-
Reference pole
2
1
Pulsed output 1
3
2
Pulsed output 2
ATTENTION
Pulsed test sources must not be used as safety-related outputs.
Emergency OFF 1
Emergency OFF 2
PO 1 2
DI 1 2
DI 3 4
1
L-
S+
PO
2 4- 8-
(2A)
1
2
3
4
5
6
1
2
3
4
5
6
DO-