background image

18 GuardPLC 8-Digital Inputs and 8-Digital Outputs Module

Publication 1753-IN010A-EN-P - October 2005

Communication Display

Communication via GuardPLC Ethernet is indicated by two small LEDs integrated
into all connecting sockets.

Specifications

LED

Status

Condition

Green

On

Full-duplex operation

Flashing

Collision

Off

Half-duplex operation, no collision

Yellow

On

Connection established

Flashing

Interface activity

Module

Response Time

≥ 10 ms

Interface: GuardPLC
Ethernet

2 x RJ-45, 10/100BaseT (with 100 Mbps) with integrated switch

Operating Voltage

24V dc, -15% to +20%, w

ss

≤ 15%

Current Consumption

max. 8 A (with max. load)
0.4 A @ 24V idle current

Isolation Voltage

No isolation between circuits

Wiring Category

(1)

category 2 on communications ports, signal ports, and power ports

Wire Size

I/O – 16 AWG (1.5 mm

2

) to 26 AWG (0.14 mm

2

) solid or stranded copper wire

rated at 75 °C (167 °F) or greater with 3/64 inch (1.2 mm) insulation max.

Power – 14 AWG (2.5 mm

2

) to 22 AWG (0.34 mm

2

) solid or stranded copper wire

rated at 75 °C (167 °F) or greater with 3/64 inch (1.2 mm) insulation max.

Terminal Block Torque

0.51 Nm (4.5 in-lb)

Fuse (external)

10 A (slow blow)

Battery Backup

none

Digital Inputs

No. of Inputs

8 (not electrically isolated)

On-state

Voltage: 15V to 30V dc
Current Consumption:

≥ 2 mA @ 15V

Off-state

Voltage: max. 5V dc
Current Consumption: max 1.5 mA (1.

0 mA @ 5V)

Switching Point

typically 7.5V

Supply

2 x 20V / 100 mA @ 24V short-circuit proof

Digital Outputs

No. of Outputs (L+)

8 (not electrically isolated), reference pole L-

Advertising