ArmorBlock 16 Input Module

Publication 1792-5.3 – October 1996

Reset Faults using Explicit Message Program Control

You can also reset inputs using the Explicit Message Program Control
feature on the Scanner module master. Refer to the specific scanner
publications for information on using this feature.

The format for the reset explicit message transaction block must
contain 6 words as shown below:

Word

Input Fault

Transaction Header

Word 0

TXID – CMD/STATUS

Word 1

PORT – SIZE

Word 2

Service = 32 hex – MAC ID

Transaction Body

Word 3

Class = 1D hex

Word 4

Instance = 1

Word 5

Attribute = 0

Attribute Data = 0