ArmorBlock 16 Input Module
Publication 1792-5.3 – October 1996
Specifications
16 Input Module – Cat. No. 1792-IB16/B
Input Specifications
Inputs per Block
16 sinking
On-state Voltage Range
10–30V dc
On-state Current
Maximum
Minimum
6.0mA @ 30V dc
2.0mA @ 10V dc
Off-state Voltage
Maximum
5V dc
Off-state Current
Minimum
1.5mA
Transition Voltage
5–10V dc
Transition Current
1.5–3.0mA
Input Impedance
Maximum
5K ohms
Input Signal Delay
Off to On
On to Off
0ms, 2ms, 4ms, 8ms, 16ms
0ms, 2ms, 4ms, 8ms, 16ms
Sensor Source
Voltage
Current
10–25V dc
50mA per point, 0.8A total per module
Indicators
Mod/Net Status – red/green
Input Fault – red
I/O Status – yellow (customer field side
driven)
General Specifications
DeviceNet Power
Voltage
Current
12.0 – 25.0V dc
100mA (no powered sensors)
900mA (full sensor load)
Surge Current at Power Up
Less than 10A for 5ms
Dimensions
Inches
Millimeters
2.63H X 7.74W X 3.06D
66.7H X 196.6W X 77.6D
Connectors
1792-IB16A/B – Aluminum connectors
1792-IB16S/B – Stainless Steel Connectors
Power Dissipation
Maximum
3.7 Watts
Thermal Dissipation Maximum
12.63 BTU/hr
Specifications continued on next page.