Connecting the input wiring, Connecting the devicenet wiring – Rockwell Automation 1792-IB16 INSTL.INST ARMOR BLOCK 16 INPT User Manual

Page 9

Advertising
background image

9

ArmorBlock 16 Input Module

Publication 1792-5.3 – October 1996

Connecting the Input Wiring

Connect input wiring to the micro connectors which screw into mating
connectors on the side of the block.

Make connections as shown below.

1

2

3

4

I/O Input Micro Connector

Pin 1 = Sensor Source Voltage Positive

Pin 2 = Signal 2

Pin 3 = Negative/Return

Pin 4 = Signal 1

(View into socket)

The signal 2 pin on the connector is used for 16 input modules only.
Use a splitter cable (or “Y” cable) to access signal 2.

Connecting the DeviceNet Wiring

Connect DeviceNet wiring to the 5-pin mini connector on the end of
the block. Connections are shown below.

1

2

3

DeviceNet Mini Connector

Pin 1 = Drain (Bare)

Pin 2 = V+ (Red)

Pin 3 = V– (Black)

(View into pins)

4

5

Pin 4 = CAN–HI (White)

Pin 5 CAN–LO (Blue)

Note: Colors are
DeviceNet standard