Cable break procedures – Rockwell Automation 1790D-XXXX DeviceNet Digital Base D-Shell Module CompactBlock LDX I/O Series B User Manual
Page 16
 
16 DeviceNet Digital Base D-shell Block CompactBlock LDX I/O
Publication
1790-IN013A-EN-P - September 2006
Cable Break Procedures
A cable break in any location between either of the following 
produces data of 0 in the data table for all inputs down stream of the 
cable break.
• Base and digital input expansion module
• Digital input expansion module and another digital input 
expansion module
Solid Green
The module is operating in a normal 
condition, and the module is online with 
connections in the established state. As 
a group 2 module, the module is 
allocated to a master.
None.
Flashing Green
The module is online with no 
connections in the established state.
Establish connections to 
other nodes. As a group 2 
module, allocate the 
module to a master.
Off
No power.
Wait until the module has 
completed the 
dup_MAC_id test or 
power the module.
I/O Status LED Indicators
Function
LED Indicator
Module 
Illumination
Condition
I/O Status
Outputs
Each output:
Green
None
Green
Output not energized.
Output energized.
Inputs
Each input:: 
Green
None
Green 
No valid input.
Valid input.
Interpret the LED Indicators
LED Indicator
Probable Cause
Recommended Action