Chapter 1 Connections

If communication with a module times out, the controller produces the following

warnings.

The I/O status indicator on the front of the controller flashes green.

A Warning ( ) icon shows over the I/O configuration folder and over the

device that has timed out.

A module fault code is produced, which you can access through:

Module Properties window for the module.

GSV instruction.

To monitor the health of your connections, use a Get System Value (GSV)

instruction to monitor the Module object for either the controller or a specific

module.

If you want to

Get this attribute

Data Type

Description

Determine if communication

has timed out with any
device

LEDStatus

INT
For efficiency, use a
DINT as the
destination data type.

Current state of the I/O status indicator on the front of the controller.
You do not enter an instance name with this attribute. This attribute applies to the entire
collection of modules.
Value

Meaning

0

Status Indicator off. No Module objects are configured for the controller
(there are no modules in the I/O Configuration section of the controller
organizer).

1

Flashing red. None of the Module objects are Running.

2

Flashing green. At least one Module object is not Running.

3

Solid green. All the Module objects are Running.

Determine if communication
has timed out with a specific

device

FaultCode

INT
For efficiency, use a
DINT as the
destination data type.

A number that identifies a module fault, if one occurs.
In the Instance Name, choose the device whose connection you want to monitor. Make sure
to assign a name to the device in the I/O Configuration folder of the project.

If Module_Status is any value other than 4, the controller is not communicating

with the module. See the following example.

14

Rockwell Automation Publication 1756-PM015F-EN-P – October 2014