Chapter 4 Change detection

access data using an MSG instruction, refer to the

Logix5000 Controllers

Messages Programming Manual

, publication

1756-PM012

.

Use these settings to read the Audit Value attribute using the Message

Configuration.

If you want to Get AuditValue in this

property

Type or select

Message Type

CIP Generic

Service Type

Audit Value Get

Source

Leave blank

Destination

tag_name of type DINT[2] or LINT 1
This tag contains the AuditValue for the controller.

ChangesToDetect Format

Bit number

Event description

0

Project stored to removable media

1

Online edits modified controller program

2

Transaction committed. Indicates that a batch of one or more changes has been applied to the
controller. For example, this might happen when a routine is imported online or when a module

configuration is changed online.

3

SFC forces enabled

4

SFC forces disabled

5

SFC forces removed

6

SFC element force value changed

7

I/O forces enabled

8

I/O forces disabled

9

I/O forces removed

10

I/O forces modified

11

Firmware update attempted

12

Firmware update from removable media attempted

13

Remote mode change

14

Keyswitch mode change

15

A major fault occurred

16

All major faults cleared

17

All major faults cleared through keyswitch

18

Task properties modified

19

Program properties modified

20

Controller time slice modified

21

Removable media removed

50