Chapter 3 Controller logging
Entry
Information Logged
Firmware update from removable media
•
Time Stamp
•
Entry Description: Firmware update from removable media
attempted
•
UserName: Local
•
Workstation: None
•
FactoryTalk Login Id: None
•
Extended Information: Old revision <major.<minor>, New
revision <major.<minor>, where the major and minor revision
numbers are each two digits.
Mode changed through Logix Designer
•
Mode change started Time Stamp
•
Entry Description: Remote mode change
•
UserName
•
Workstation Name
•
FactoryTalk Login Id
•
Extended Information: Old mode <mode>, New mode <mode>
•
Possible modes:
−
Run
−
Remote Run
−
Test
−
Program
−
Remote Program
Mode changed through keyswitch
•
Time Stamp
•
Entry Description: Keyswitch mode change
•
UserName: Local
•
Workstation Name: None
•
FactoryTalk Login Id: None
•
Extended Information: Old mode <mode>, New mode <mode>
•
Possible modes:
−
Run
−
Remote Run
−
Test
−
Program
−
Remote Program
Major fault
•
Time Stamp
•
Entry Description: A major fault occurred
•
UserName: None
•
Workstation Name: None
•
FactoryTalk Login Id: None
•
Extended Information: Fault type <type number>, Fault code
<code number>
42
Rockwell Automation Publication 1756-PM015F-EN-P – October 2014