Compact™ 1769-OF2 (Series B or Later) Analog Output Module 13
Publication 1769-IN049A-EN-P
Wire Size and Terminal Screw Torque
Each terminal accepts up to two wires with the following restrictions:
I/O Memory Mapping
Output Data File
For each module, slot x, words 0-1 in the output data file contain the
channel 0 and channel 1 output data.
• SGN = Sign bit in two’s complement format.
Wire Type
Wire Size
Terminal Screw
Torque
Retaining Screw
Torque
Solid
Cu-90°C (194°F)
#14 to #22 AWG
0.68 Nm (6 in-lbs)
0.46 Nm (4.1 in-lbs)
Stranded
Cu-90°C (194°F)
#16 to #22 AWG
0.68 Nm (6 in-lbs)
0.46 Nm (4.1 in-lbs)
Wo
rd
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
SGN
Analog Output Data Channel 0
1
SGN
Analog Output Data Channel 1