I/o memory mapping, Wire size and terminal screw torque, Output data file – Rockwell Automation 1769-OF2 Compact (Series B or Later) Analog Output Module User Manual

Page 13

Advertising
background image

Compact™ 1769-OF2 (Series B or Later) Analog Output Module 13

Publication 1769-IN049A-EN-P

Wire Size and Terminal Screw Torque

Each terminal accepts up to two wires with the following restrictions:

I/O Memory Mapping

Output Data File

For each module, slot x, words 0-1 in the output data file contain the
channel 0 and channel 1 output data.

• SGN = Sign bit in two’s complement format.

Wire Type

Wire Size

Terminal Screw

Torque

Retaining Screw

Torque

Solid

Cu-90°C (194°F)

#14 to #22 AWG

0.68 Nm (6 in-lbs)

0.46 Nm (4.1 in-lbs)

Stranded

Cu-90°C (194°F)

#16 to #22 AWG

0.68 Nm (6 in-lbs)

0.46 Nm (4.1 in-lbs)

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

SGN

Analog Output Data Channel 0

1

SGN

Analog Output Data Channel 1

Advertising