6 Compact™ 1769-OF2 (Series B or Later) Analog Output Module

Publication 1769-IN049A-EN-P

Mounting Expansion I/O

Minimum Spacing

Maintain spacing from
enclosure walls,
wireways, adjacent
equipment, etc. Allow
50 mm (2 in.) of space
on all sides for
adequate ventilation, as
shown:

Panel Mounting

Mount the module to a panel using two screws per module. Use M4 or #8
panhead screws. Mounting screws are required on every module.

Panel Mounting Using the Dimensional Template

!

ATTENTION

During panel or DIN rail mounting of all devices, be sure
that all debris (metal chips, wire strands, etc.) is kept
from falling into the module. Debris that falls into the
module could cause damage on power up.

Top

Bottom

Side

Side

Host Controller

C

om

pac

t I/

O

C

om

pac

t I/

O

C

om

pac

t I/

O

C

om

pac

t I/

O

C

om

pac

t I/

O

End Ca

p

H

ost

C

on

tr

olle

r

Co

mp

ac

t I

/O

Co

mp

ac

t I

/O

Co

mp

ac

t I

/O

En

d C

ap

132 (5.197)

122.6±0.2

(4.826±0.008)

35

(1.38)

28.5

(1.12)

Refer to host controller documentation for this dimension.

For more than 2 modules: (number of modules-1) X 35mm (1.38 in.)

NOTE: All dimensions are in mm (inches).
Hole spacing tolerance: ±0.4 mm (0.016 in.)