16 Compact™ 1769-OF2 (Series B or Later) Analog Output Module
Publication 1769-IN049A-EN-P
Channel Configuration Words
Words 0 through 1 of the configuration file allow you to change the
parameters of each channel independently. For example, word 0
corresponds to channel 0.
Define
These bit settings
Indicate this
15
14
13
12
11
10
9
8
4-7
3
2
1
0
Program
(Idle) to
Fault
Enable
No
t Use
d
No
t Use
d
0
Program (Idle) Mode
Data Applied
(1)
(1) These functions are not supported by all controllers (e.g. MicroLogix 1500) using any configuration method.
Refer to your controller manual for details.
1
Fault Mode Data
Applied
Not Used
(Reserved)
Program
(Idle) Mode
0
Hold Last State
1
User-Defined
Value
Fault Mode
0
Hold Last State
1
User-Defined Fault
Value
Output
Range
Select
0
0
0
0
-10V dc to +10V dc
0
0
0
1
0 to 5V dc
0
0
1
0
0 to 10V dc
0
0
1
1
4 to 20 mA
0
1
0
0
1 to 5V dc
0
1
0
1
0 to 20 mA
Spare
(2)
(2) Any attempt to write a non-valid (spare) bit configuration into any selection field results in a module
configuration error.
Output
Data
Select
0
0
0
Raw/Proportional
Data
0
0
1
Engineering Units
0
1
0
Scaled-for-PID
0
1
1
Percent Range
Spare
Enable
Channel
1
Enabled
0
Disabled