Output specifications – Rockwell Automation 1769-OF2 Compact (Series B or Later) Analog Output Module User Manual

Page 18

Advertising
background image

18 Compact™ 1769-OF2 (Series B or Later) Analog Output Module

Publication 1769-IN049A-EN-P

Output Specifications

Specification

1769-OF2 (Series B or later)

Analog Normal Operating Ranges

(1)

(1) The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The

module will continue to convert the analog input up to the maximum full scale range. The flag automatically
resets when within the normal operating range.

Voltage: ± 10V dc, 0 to 10V dc, 0 to 5V dc, 1 to 5V dc
Current: 0 to 20 mA, 4 to 20 mA

Full Scale Analog Ranges

(1)

Voltage: ± 10.5V dc, -0.5 to 10.5V dc, -0.5 to 5.25V dc,
0.5 to 5.25V dc

Current: 0 to 21 mA, 3.2 to 21 mA

Number of Outputs

2 single-ended

Bus Current Draw (max.)

120 mA at 5V dc
120 mA at 24V dc

(2)

(2) If the optional 24V dc Class 2 power supply is used, the 24V dc current draw from the bus is 0 mA.

Heat Dissipation

2.63 Total Watts

(The Watts per point, plus the minimum

Watts, with all points energized.)

Converter Type

Sigma-Delta

Digital Resolution Across Full
Range

14 bits (unipolar); 14 bits plus sign (bipolar)

±10V dc: Sign + 14 bits, 0.64 mV
0 to +5V dc: Sign + 13 bits, 0.64 mV
0 to +10V dc: Sign + 14 bits, 0.64 mV
+4 to +20 mA: Sign + 14 bits, 1.28 µA
+1 to +5V dc: Sign + 13 bits, 0.64 mV
0 to +20 mA: Sign + 14 bits, 1.28 µA

Conversion Rate (all channels) max. 2.5 ms

Step Response to 63%

(3)

(3) Step response is the period of time between when the D/A converter was instructed to go from minimum to

full range until the device is at 63% of full range.

2.9 ms

Current Load on Voltage Output

10 mA max.

Resistive Load on Current Output

0 to 500

(includes wire resistance)

Load Range on Voltage Output

> 1 k

at 10V dc

Max. Inductive Load
(Current Outputs)

0.1 mH

Max. Capacitive Load
(Voltage Outputs)

1 µF

Field Calibration

None required

Overall Accuracy

(4)

(4) Includes offset, gain, drift, non-linearity and repeatability error terms.

Voltage Terminal: ±0.5% full scale at 25°C
Current Terminal: ±0.35% full scale at 25°C

Advertising