20 Compact™ 1769-OF2 (Series B or Later) Analog Output Module

Publication 1769-IN049A-EN-P

Hazardous Location Considerations

This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D
or non-hazardous locations only. The following ATTENTION statement
applies to use in hazardous locations.

Specification

1769-OF2 (Series B or later)

System Power Supply
Distance Rating

8 (The module may not be more than 8 modules away from the
system power supply.)

Optional 24V dc Class 2 Power
Supply Voltage Range

(1)

(1) Failure to use a Class 2 power supply without regulation within these limits could result in improper module

operation.

20.4 V to 26.4 V dc

Recommended Cable

Belden™ 8761 (shielded)

Vendor I.D. Code

1

Product Type Code

10

Product Code

32

!

WARNING

EXPLOSION HAZARD

• Substitution of components may impair suitability for

Class I, Division 2.

• Do not replace components or disconnect equipment

unless power has been switched off or the area is
known to be non-hazardous.

• Do not connect or disconnect components unless

power has been switched off or the area is known to
be non-hazardous.

• This product must be installed in an enclosure.

• All wiring must comply with N.E.C. article 501-4(b).