Hazardous location considerations – Rockwell Automation 1769-OF2 Compact (Series B or Later) Analog Output Module User Manual
Page 20

20 Compact™ 1769-OF2 (Series B or Later) Analog Output Module
Publication 1769-IN049A-EN-P
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D
or non-hazardous locations only. The following ATTENTION statement
applies to use in hazardous locations.
Specification
1769-OF2 (Series B or later)
System Power Supply
Distance Rating
8 (The module may not be more than 8 modules away from the
system power supply.)
Optional 24V dc Class 2 Power
Supply Voltage Range
(1)
(1) Failure to use a Class 2 power supply without regulation within these limits could result in improper module
operation.
20.4 V to 26.4 V dc
Recommended Cable
Belden™ 8761 (shielded)
Vendor I.D. Code
1
Product Type Code
10
Product Code
32
!
WARNING
EXPLOSION HAZARD
• Substitution of components may impair suitability for
Class I, Division 2.
• Do not replace components or disconnect equipment
unless power has been switched off or the area is
known to be non-hazardous.
• Do not connect or disconnect components unless
power has been switched off or the area is known to
be non-hazardous.
• This product must be installed in an enclosure.
• All wiring must comply with N.E.C. article 501-4(b).