Configuring FactoryTalk Security with Logix Designer application Chapter 2

Tip:

If you cannot log on to FactoryTalk, see "I cannot log on to the FactoryTalk

Directory" in FactoryTalk Help.

6. Open the RSLogix 5000 Feature Security Properties dialog box:

a. In Windows Explorer, browse to System, then go to Policies, then

go to Product Policies, and then go to RSLogix 5000.

b. Right-click Feature Security and then click Properties.

7. Secure the RSLogix 5000 controller:

a. In the Feature Security Properties dialog box, select

Controller:Secure and then click Browse.

b. In the Configure Securable Action dialog box, click Add to select

the user accounts or groups that you want to configure.

c. In the Select User and Computer dialog box, select the user

accounts or groups and click OK.

d. Follow the instructions to complete the configuration.

If you find that the Security feature is not enabled in the Logix Designer

application, then you need to make sure FactoryTalk Services Platform (FTSP)

software is installed properly.

Follow these instructions to install the FTSP software.

1. On the installation disk, browse to \System\FTSP and double-click the

Setup.exe file.

2. Follow the installation prompts to complete the installation.

The installation automatically configures and backs up all existing local and

network FactoryTalk Directory files. For new installations, it backs up the

pre-configured FactoryTalk Directory files. The backups let you restore the

Factory Talk Directory files to a previous software version.

After the installation is complete, refer back to

Enabling security

on

page 11

.

If you are having problems, refer to the

FactoryTalk Security System

Configuration Guide

, publication

FTSEC-QS001

.

Installing FactoryTalk
Services Platform software

Rockwell Automation Publication 1756-PM016G-EN-P - October 2014