Chapter 4 Configuring source protection in the Logix Designer application

Protecting components

The Source Protection Configuration dialog box lists all Program Routines,

Add-On Instructions, and Equipment Phase State Routines in the project file.

You protect these components by applying source keys. Source keys are

user-generated passwords used to lock components. Users that do not have the

source key for a component are not able to modify the component and may not be

able to view the component.

About source keys

In version 18 and earlier of RSLogix 5000 software, only IEC-61131 compliant

source keys are recognized. Each source key must begin with a lowercase character

a-z or underscore character ( _ ), and contain only characters lowercase a-z, 0-9,

and an underscore character ( _ ). You can enter uppercase A-Z characters in

RSLogix 5000 software or in the source key file, but the uppercase characters are

converted to lowercase. Source keys are limited to 40 characters in length.

In version 19 and later of the application, source keys are case-sensitive and may

contain any printable ASCII character, excluding the space character. This

includes uppercase A-Z, lowercase a-z, numbers 0-9, and symbols such as "!@#$%.

Source keys are limited to 40 characters in length.

Source key names

Version 19 and later of the application supports associating names with source

keys. Source key names are descriptive text that help identify source keys. Where

appropriate, Logix Designer application will display the source key name in place

of the source key itself. This provides an additional layer of security for the source

key.

34

Rockwell Automation Publication 1756-PM016G-EN-P - October 2014