General Specifications

Specification

Value

Dimensions, H x W x D

90 x 40 x 87 mm

height including mounting tabs is 110 mm
3.543 x 1.5753 x 3.425 in.

height including mounting tabs is 4.33 in.

Approximate Shipping Weight

(with carton)

228 g (0.50 lbs.)

Temperature, nonoperating

-40…85 °C (-40…185 °F)

Temperature, operating

0…55 °C (-32…131 °F)

Operating humidity

5…95% non-condensing

Operating altitude

2000 m (6561 ft)

Vibration

Refer to the MicroLogix 1200 Controllers Installation Instructions,
publication

1762-IN006

.

Shock, operating

Hazardous Environment Class

Class I, Division 2, Hazardous Location, Groups A, B, C, D

ISA/ANSI 12.12.01

(C-UL under CSA C22.2 No. 213)

Noise Immunity

NEMA standard ICS 2-230

Radiated and Conducted Emissions

EN50081-2 Class A

ESD Immunity (IEC1000-4-2)

4 kV contact, 8 kV air, 4 kV indirect

Radiated Immunity (IEC1000-4-3)

10 V/m, 80 to 1000 MHz, 80% amplitude modulation, +900 MHz
keyed carrier

Fast Transient Burst (IEC1000-4-4)

2 kV, 5 kHz

Surge Immunity (IEC1000-4-5)

2 kV common mode, 1 kV differential mode

Conducted Immunity (IEC1000-4-6)

10V, 0.15…80 MHz

(1)

(1)

Conducted Immunity frequency range may be 150 kHz…30 MHz if the Radiated Immunity frequency range is 30…1000
MHz.