Rockwell Automation 1762-OW8 MICROLOGIX RELAY OUTPUT MODULE User Manual

Page 12

Advertising
background image

12

MicroLogix 1762-OW8 Relay Output Module

Publication 1762-IN003B-EN-P - June 2013

Certifications

Certification (when product is
marked)

(1)

(1)

See product certification link at

http://www.rockwellautomation.com/products/certification

for Declaration of Conformity,

Certificates, and other certification details.

Value

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,

certified for U.S and Canada.

See UL File E334470.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

European Union 2006/95/EC LVD, compliant with:

EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Autralian Rediocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

KC

Korean Registration of Broadcasting and Communications Equipment,

compliant with:

Article 58-2 of Radio Waves Act, Clause 3

Output Specifications

Specification

Value

Voltage category

AC/DC normally open relay

Operating voltage range

5…265V AC

5…125V DC

Number of outputs

8

Bus current draw (max.)

80 mA @ 5V DC (0.40W)
90 mA @ 24V DC (2.16W)

Heat dissipation (max.)

2.9 Total Watts

Signal delay (max.) – resistive load

On Delay: 10 ms
Off Delay: 10 ms

Off-state leakage (max.)

0 mA

On-state current (min.)

10 mA @ 5V DC

Continuous current per point (max.)

2.5 A (

See “Relay Contact Ratings” on page 13.

)

Continuous current per common
(max.)

8 A

Continuous current per module (max.) 16 A

Advertising